Martindale MARVI13800
Voltage Indicator
Product Overview
The Martindale VI13700 has been widely used for many years and as part of its design has always included a fuse in the probe to limit the current in the event of damage to the cable.
There is a technical argument that fuses in a voltage indicator can cause unreliability and any problem with the fuse could cause the voltage indicator not to indicate a hazardous voltage. In reality this risk is very small and correct proving procedures will identify the problem. None the less, because of this potential problem, BS EN61243-3 prohibits the use of fuses in 2 pole voltage indicators.
NB Proper proving procedures should always be used with any voltage indicator.
Product Specs
- Nominal Voltage Range: 50 - 600V AC / DC
- Nominal Voltage Threshold Indications: 50, 100, 200, 400 V DC/AC rms
- Nominal Voltage threshold tolerance: < 85% of marked threshold indication
- Polarity indication: from approx 12V DC/AC rms
- AC/DC voltage detection: automatic
- Range detection: automatic
- Response time: < 0.1s
- Frequency range: DC, 1 - 400 Hz
- Test current: < 3.5mA at 600V DC/AC rms
- Duty ratio: 30s ON (operated) / 240s OFF (recovery)
Environmental
- Temperature & Humidity (operating & storage): -10°C to 55°C ≤ 85% R.H. / -10°C to 55°C ≤ 85% R.H.
- Altitude: up to 2000m
- IP rating: IP54
General
- Power: from circuit under test
- Dimensions: 205(L) x 67(W) x 27(D) mm
- Weight: 130g approx.
- Includes: instructions
Safety
- Conforms to BS EN 61243-3:2010 CAT IV 600 V, CAT III 1000V
- Class II, Double Insulation
- Pollution Degree: 2
- EMC: Conforms to BS EN 61326-1
- Voltage Indication
- Safe Isolation Procedures & Proper Equipment Save Lives
- Stiffer penalties for Electricity at Work violations